Skip to main content Skip to search Skip to main navigation Skip to B2B platform navigation
The REGARD 7000 Relay Module 24 V DC has 8 potential-free switching contacts. All switching contacts are SIL2c3 compliant. The relays can be used in operating current and static current operation. They can be triggered by alarms and special signals. The „degradation scheme“ can be used to select how to proceed in case of the failure of a measurement and how to treat it. It can be treated conventionally as an error or else as an alarm. There is also the possibility to combine alarms and special signals in a selectable alarm to provide more safety. For ideal adaptation to the triggering alarm devices the activation delay can be set to a value between 0 seconds and 100 minutes and the deactivation delay between 0 seconds and 100 minutes. The relays can be locked individually or in groups, manually or via special signal from the transmitter. The configuration and setting of parameters take place via the REGARD 7000 Dashboard and is supported by assistance systems and copy functions. - Number of output relays: 8 with each a switching contact - Switching voltage: 5 to 24 V DC - Switching current: 10 mA to 2 A - Power consumption: max. 100 mA (no relay activated), max. 200 mA (8 relays activated) - Power loss: 5 W at 24 V - Update rate of switching outputs: 0.5 s - Temperature (during operation): 0 ... 50 °C -Temperature (in storage): –20 ... +60 °C - Humidity (during operation): 20 ... 90 % r.h., non condensing - Humidity (in storage): 5 ... 90 % r.h., non condensing - Complies with the requirements of the electromagnetic compliance according to EN 50270:2015 (type 2) - Size and weight [H x B x T] [110 x 46 x 130] [mm] [340] [g]