Methane/propane calibrated receiver element of the explosion-proof open path gas detector system with dual wavelength infrared absorption technology. Receiver supplied with mounting plate, stainless steel 316L Marine junction box Ex e (4xM25), fire-resistant cable and protective cover. Housing IP 66/67, stainless steel 316L, dimensions (wxhxd, approx.): 430x670x470 mm, weight (approx.): 10 kg ATEX/IECEx approval: II 2 (1) G Ex db [ia Ga] IIC T6/T5 Gb, -55 to +40/+60 °C II 2 (1) D Ex tb [ia Da] IIIC T80 °C/T95 °C Db Metrological report: IEC/EN 60079-29-4, FM6325 Safety integrity level: SIL 2 Tx L transmitter for 100-200 m system, to be ordered separately -Dräger grants a manufacturer’s warranty of 3 years